4. Type Tests
RuggedCom® RuggedSwitch® 25 M2100 Installation Guide Rev 1.0
Test Description Test Levels
Severity
Levels
AC Power ports 2 kVAC N/A
Signal ports 5 kV (Fail-Safe Relay output) N/A
DC Power ports 5 kV N/AIEC 60255-5 H.V. Impulse
AC Power ports 5 kV N/A
Table 4.1. IEC 61850-3 Type Tests
4.2. IEEE 1613 Type Tests
Test Description Test Levels
Enclosure Contact ± 8 kV
IEEE C37.90.3 ESD
Enclosure Air ± 15 kV
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m
Signal ports ± 4 kV @ 2.5 kHz
DC Power ports ± 4 kV
AC Power ports ± 4 kV
IEEE C37.90.1 Fast Transient
Earth ground ports ± 4 kV
Signal ports 2.5 kV common mode @ 1 MHz
DC Power ports
2.5 kV common, 1 kV
diff. mode @ 1 MHz
IEEE C37.90.1 Oscillatory
AC Power ports
2.5 kV common, 1 kV
diff. mode @ 1 MHz
Signal ports 5 kV (Fail-Safe Relay output)
DC Power ports 5 kVIEEE C37.90 H.V. Impulse
AC Power ports 5 kV
Signal ports 2 kVAC
DC Power ports 1.5 kVDCIEEE C37.90 Dielectric Strength
AC Power ports 2 kVAC
Table 4.2. IEEE 1613 Type Tests
4.3. Military Standard Tests
Test Description Test Levels
MIL-STD-901D Shock (Hard-Mounted)
Grade A, Equipment Class
I, Shock Type A Equipment
MIL-STD-167-1 Vibration Type I (Upper Frequency of 33 Hz)