3. Technical Specifications
RuggedCom® RuggedSwitch® 20 M2100 Installation Guide Rev 1.0
3. Technical Specifications
3.1. Power Supply Specifications
Input Range Max. Power Consumption
a
Power Supply Type
Min Max
Internal
Fuse Rating
10/100TX FE Ports Worst Case
12 - 24 VDC 10 VDC 36 VDC 6.3 A(F)
b
15 W 30 W
48 VDC 36 VDC 59 VDC 3.15 A(T)
b
15 W 30 W
HI (125/250 VDC)
c
88 VAC 300 VDC 2 A(T)
cb
15 W 30 W
HI (110/230 VAC)
c
85 VAC 264 VAC 2 A(T)
cb
15 W 30 W
a
Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1W less than fiber optic ports.
b
(F) Denotes fast-acting fuse (T) denotes time-delay fuse.
c
The "HI" power supply is the same power supply for both AC and DC.
Table 3.1. Power Supply Specifications
3.2. Failsafe Relay Specifications
Parameter Value (Resistive Load)
Max Switching Voltage 240 VAC, 125 VDC
Rated Switching Current 2 A @ 240 VAC, 0.15 A @ 125 VDC, 2 A @ 30 VDC
Max Switching Capacity 150 W, 500 VA
Table 3.2. Failsafe Relay Specifications
3.3. Networking Standards Supported
Parameter 10 Mbps Ports 100 Mbps Ports 1000 Mbps Ports Notes
IEEE 802.3 Yes 10BaseT / 10BaseFL
IEEE 802.3u Yes 100BaseTX / 100BaseFX
IEEE 802.3z Yes 1000BaseSX/LX
IEEE 802.3ab Yes 1000BaseTx
IEEE 802.3x Yes Yes Yes Full Duplex Operation
IEEE 802.1D Yes Yes Yes MAC Bridges
IEEE 802.1Q Yes Yes Yes VLAN (Virtual LAN)
IEEE 802.1p Yes Yes Yes Priority Levels
Table 3.3. Networking Standards Supported
3.4. Twisted-Pair Port Specifications
Parameter Specification Notes
Speed 10/100 Mbps Auto-negotiating